Application
Suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switch boards and power stations. Due to the good laying characteristic, this cable can also be installed in difficult in difficult line guide ways.
Cable Construction
Circular bare aluminum-conductor of stranded wires
Inner semi-conducting coating
Conductor insulation of cross-linked Polyethylene (XLPE)
Outer extrusion of semi-conducting coating spliced with the insulation
Wrapping of conductive material
Shield: Braiding of copper wires with one or two tapes applied helically
Wrapping
PVC outer jacket
Jacket color: Red or black
Technical Data
Temperature Range
During installation up to -5°C
Operating Temperature
Max. +90°C
Short Circuit Temperature +250°C
(Short circuit duration up to 5 sec.)
Nominal Voltages
U0/U 6/10 kV, 12/20 kV, 18/30 kV
Operating Voltages for
6/10 kV = max. 12 kV
12/20 kV = max. 24 kV
18/30 kV = max. 36 kV
Test Voltages for
6/10 kV = 15 kV
12/20 kV = 30 kV
18/30 kV = 45 kV
Minimum Bending Radius
During installation max. 15x cable Ø
No. of cores |
Shape of the conductor |
Diameter appr. |
Cable mass appr. |
Radius of bend |
Effect. resist. of conductors |
Capacity |
(mm2) |
|
(mm) |
(kg/km) |
(mm) |
(/km) |
(µH/km) |
1x35/16 |
RMV |
25 |
750 |
375 |
0,868 |
0,223 |
1x50/16 |
RMV |
26 |
815 |
397 |
0,641 |
0,245 |
1x70/16 |
RMV |
28 |
910 |
420 |
0,443 |
0,277 |
1x95/16 |
RMV |
30 |
1040 |
450 |
0,320 |
0,311 |
1x120/16 |
RMV |
31 |
1140 |
465 |
0,253 |
0,341 |
1x150/25 |
RMV |
32 |
1350 |
487 |
0,206 |
0,371 |
1x185/25 |
RMV |
34 |
1500 |
510 |
0,164 |
0,405 |
1x240/25 |
RMV |
37 |
1700 |
555 |
0,125 |
0,450 |
1x300/25 |
RMV |
39 |
1930 |
585 |
0,100 |
0,496 |
1x400/35 |
RMV |
42 |
2350 |
630 |
0,078 |
0,555 |
1x500/35 |
RMV |
45 |
2750 |
682 |
0,061 |
0,612 |