10kv 20kv 30kv N2XSY NA2XSY XLPE Power Cable

10kv 20kv 30kv N2XSY NA2XSY XLPE Power Cable

Model No.︰N2XSY NA2XSY

Brand Name︰HESHENG

Country of Origin︰China

Unit Price︰US $ 5 / meter

Minimum Order︰1000 meter

Inquire Now

Product Description

Application  
Suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switch boards and power stations. Due to the good laying characteristic, this cable can also be installed in difficult in difficult line guide ways.

Cable Construction  
Circular bare aluminum-conductor of stranded wires
Inner semi-conducting coating
Conductor insulation of cross-linked Polyethylene (XLPE)
Outer extrusion of semi-conducting coating spliced with the insulation
Wrapping of conductive material
Shield: Braiding of copper wires with one or two tapes applied helically
Wrapping
PVC outer jacket
Jacket color: Red or black

 

Technical Data
Temperature Range
During installation up to -5°C
Operating Temperature
Max. +90°C
Short Circuit Temperature +250°C
(Short circuit duration up to 5 sec.)


Nominal Voltages
U0/U 6/10 kV, 12/20 kV, 18/30 kV
Operating Voltages for
6/10 kV = max. 12 kV
12/20 kV = max. 24 kV
18/30 kV = max. 36 kV


Test Voltages for
6/10 kV = 15 kV
12/20 kV = 30 kV
18/30 kV = 45 kV


Minimum Bending Radius
During installation max. 15x cable Ø

 

No. of cores Shape of the conductor Diameter appr. Cable mass appr. Radius of bend Effect. resist. of conductors Capacity 
(mm2)   (mm) (kg/km) (mm) (/km) (µH/km)
1x35/16 RMV 25 750 375 0,868 0,223
1x50/16 RMV 26 815 397 0,641 0,245
1x70/16 RMV 28 910 420 0,443 0,277
1x95/16 RMV 30 1040 450 0,320 0,311
1x120/16 RMV 31 1140 465 0,253 0,341
1x150/25 RMV 32 1350 487 0,206 0,371
1x185/25 RMV 34 1500 510 0,164 0,405
1x240/25 RMV 37 1700 555 0,125 0,450
1x300/25 RMV 39 1930 585 0,100 0,496
1x400/35 RMV 42 2350 630 0,078 0,555
1x500/35 RMV 45 2750 682 0,061 0,612

Payment Terms︰ T/T, L/C at sight